LCD Display Messages and Troubleshooting
Warnings
-
W01 Memory fault: Issue with datalogger memory. Action: Contact technical assistance.
-
W02 Unset nation: The nation setting is missing. Action: Select the nation of installation as per the 'Choosing the nation' section.
-
W03 Unset clock: Date not set. Action: Set the date via the ‘SETTINGS’ Menu.
-
W04 Fan anomaly: Indicates a fan problem. Action: Turn off the inverter, check for foreign objects in the fan, and if necessary, contact technical assistance.
-
W05 High °C: Inverter temperature is high. Action: Check installation site requirements. If the alarm persists after a prolonged shutdown, contact technical assistance.
-
W06 Low °C: Room temperature is too low or temperature sensors are faulty. Action: Check inverter operation during central hours of the day and/or sensor reliability.
-
W08 Derating P/I: Inverter operating with limited power. Action: Refer to the Efficiency and power limitation section.
-
W09 Low Vdc: Input voltage is low; inverter in standby before starting. Action: This is normal in certain conditions; no action needed unless persistent.
-
W10 Low DC power: Low power available from PV generator; inverter goes into standby. Action: Check if panels are covered with snow or dirty and clean if necessary.
-
W11 Grid timeout: Grid outside limits for over 10 minutes in 'Check AC'. Action: Wait for reconnection.
-
W12 Plow timeout: Output power too low for too long, inverter enters standby. Action: Wait for reconnection.
-
W13 Precharge KO: Bulk capacitors loading longer than expected. Action: This is normal at sunrise/sunset or if panels are dirty or covered with snow.
-
W14 REP command: Output power limited by grid operator. Action: No action required.
-
Start ramp: Initial output power limitation ramp in progress. Action: No action required.
-
W16 Boost fault: Input converter fault. Action: Contact technical assistance.
System Malfunctions
-
A02 Fac outrange: Grid frequency outside limits. Action: Wait for reconnection.
-
A03 Low Vac: Grid voltage outside limits. Action: Check AC system, contact your energy distributor.
-
A04 High Vac/A05 High avg Vac: Average grid voltage outside limits. Action: Same as above.
-
A06 Weak grid: Output power limited due to high grid voltage. Action: No immediate action required; check if adjustment needed.
-
A07 High Vdc: Input voltage exceeds maximum no-load voltage. Action: Verify system size.
-
A08 No Grid: No grid voltage present, inverter switches off if condition persists. Action: Wait for reconnection.
-
A09 Grid anomaly: Grid voltage or frequency outside limits. Action: Check AC system, contact your energy distributor.
-
A10 Overfrequen.: Output power limited according to grid frequency. Action: No action required.
-
A11 Emergency: Feeding interrupted by emergency command from grid operator. Action: Wait for resolution.
Inverter Problems
-
F01 High V_bulk+/F03 High V_bulk-/F03 High V_bulk: Internal voltage too high. Action: Contact technical assistance for 1.5kW – 2kW versions; 3kW version will restart by itself.
-
F04 Bulk balance: Internal bulk capacitors unbalanced. Action: Inverter will restart by itself.
-
F05 High °C: High temperature or faulty sensors. Action: Check installation site requirements; contact technical assistance if issue persists.
-
F06 Link fail: Inverter does not detect internal devices. Action: Contact technical assistance.
-
F07 Insulat. KO: Negative isolation resistance verification. Action: Check the system; if problem persists, contact for further assistance.
-
F08 DC injection: Too high DC current input on the grid. Action: Wait for grid reconnection.
Inverter Faults
-
L01 Data bus KO to L21 Autotest KO: Various communication, memory, and sensor issues. Action for all: Contact technical assistance or follow specific instructions provided for resetting or checking the installation.
-
L28 Iac sens. KO: Output current sensor fault. Action: Contact technical assistance.
Operating Conditions and Status Messages
-
Off - No Display
-
Description: The PV inverter is completely off. The VDC is below the “Working range.”
-
Standby - Waiting
-
Description: Input voltage (VDC) is below the "Working range" but above "Shutdown voltage."
-
Powered On and Waiting - Ready…
-
Description: Input voltage is within the "Working range" but below the "Initial feed-in voltage." The inverter is ready to supply current once voltage exceeds this threshold.
-
Grid Feed-In Control - Checking
-
Description: When voltage exceeds "Initial feed-in voltage," the inverter verifies feed-in conditions and initiates a countdown.
-
Grid Feed-In, MPPT - Connected to Grid
-
Description: The inverter is supplying current to the grid. After 10 seconds, the power being supplied is displayed.
-
Firmware Update - FLASH FLASH
-
Description: Firmware update is in progress.
Monitoring Parameters
-
Instantaneous Output Power - Pac=xxxxW
-
Description: Real-time output power in watts (W).
-
Accumulated Energy - Energy=xxxxxxkWh
-
Description: Total energy supplied to the grid since inverter installation.
-
Grid Voltage - Vac=xxx.xV
-
Description: Grid voltage in volts AC (VAC).
-
Grid Frequency - Frequency=xx.xHz
-
Description: Grid frequency in hertz (Hz).
-
Grid Current - AC Current=xx.xA
-
Description: Current supplied to the grid in amperes (A).
-
PV Input Voltage - Vdc=xxx.xV
-
Description: Input voltage from PV panels in volts (V).
System Faults
-
Insulation Anomaly - Err. Aislamiento
-
Description: Ground insulation fault in the PV generator or input surge protection triggered.
-
Ground Fault Circuit Interrupter (GFCI) Active - Err. Tierra
-
Description: Excessive leakage current to ground.
-
Network Fault - Fallo de red
-
Description: Measured network data (voltage, frequency) is out of tolerance.
-
Abnormal Network Impedance - Err. Impedancia
-
Description: Network impedance exceeds permissible levels, or impedance change (ΔZ) is above the limit.
-
Grid Unavailable - Red no presente
-
Description: The AC grid is unavailable.
-
High DC Input Voltage - Sobretensión DC
-
Description: Input voltage exceeds the "Max. open DCV" threshold.
Inverter Faults
-
Reading Consistency Error - Err. Micros
-
Description: Inconsistent AC parameter readings (voltage, frequency, leakage current, DC injection) from the microprocessors.
-
High Temperature - Sobretemperatura
-
Description: Internal temperature exceeds normal operating limits.
-
Output Relay Fault - ERR. Contactor AC
-
Description: The relay between the inverter and the grid is not functioning correctly.
-
High DC Output Current - Nivel DC alto
-
Description: Excessive DC current injection on the output.
-
EEPROM Error - ERR. EEPROM
-
Description: Issues with reading data from the internal EEPROM.
-
Microprocessor Communication Error - ERR. COM
-
Description: Communication issue between microprocessors.
-
High Internal Bus Voltage - FALLO CC ALTO
-
Description: Internal bus voltage is too high.
-
Low Internal Bus Voltage - FALLO CC BAJO
-
Description: Internal bus voltage is too low.
-
Reference Voltage Error (2.5V) - ERR. REF 2.5V
-
Description: Anomaly in the internal 2.5V reference voltage.
-
DC Output Sensor Fault - ERR SENSOR DC
-
Description: Anomaly in the DC output sensor.
Inverter Information and Display Messages
-
Model Display - XXXX W
-
Description: Displays the inverter model.
-
LCD Contrast Adjustment - Ajuste contraste
-
Description: Allows adjustment of the screen contrast.
-
LCD Lock - LCD bloqueado
-
Description: Holds the currently displayed message on the screen.
-
Reconnect Wait Time - Reconexión xxx s
-
Description: Time remaining before reconnecting to the grid.
-
Firmware Version - Firmware xx.xx
-
Description: Displays the firmware version information.
-
Language Setting - Ajuste idioma
-
Description: Sets the display language.