Input Side |
|
|
|
Absolute max DC input voltage |
1100 V |
1100 V |
1100 V |
Start-up DC input voltage |
250-500 V |
250-500 V |
250-500 V |
Operating DC input voltage range |
200-1000 V |
200-1000 V |
200-1000 V |
Rated DC input voltage |
620 V |
620 V |
620 V |
Rated DC input power |
10200 W |
12760 W |
15300 W |
No. of independent MPPT |
2 |
2 |
2 |
Max photovoltaic power recommended |
14500 Wp |
18125 Wp |
21750 Wp |
Max DC input power for each MPPT |
7800 W |
8300 W |
10000 W |
MPPT input DC voltage range at Pacr |
460-850 V |
460-850 V |
460-850 V |
Max DC input current for each MPPT |
2x17 A |
2x18 A |
2x22 A |
Max input short circuit current |
30 A |
30 A |
30 A |
No. of DC input pairs for each MPPT |
2 |
2 |
2 |
DC connection type |
PV quick fit connector |
PV quick fit connector |
PV quick fit connector |
Input protection |
Reverse polarity protection, input over voltage protection, isolation control |
|
|
Output Side |
|
|
|
AC grid connection type |
Three-phase |
Three-phase |
Three-phase |
Earthing system |
TN-S, TN-C, TN-CS, TT |
TN-S, TN-C, TN-CS, TT |
TN-S, TN-C, TN-CS, TT |
Rated AC power |
10000 W |
12500 W |
15000 W |
Max AC output power |
10000 W |
12500 W |
15000 W |
Max apparent power |
10000 VA |
12500 VA |
15000 VA |
Max reactive power |
6000 VAR |
7500 VAR |
9000 VAR |
Nominal power factor |
> 0.995; adjustable 0.8-1 inductive/capacitive |
|
|
Rated AC output voltage |
380V, 400V |
380V, 400V |
380V, 400V |
Max AC output current |
16 A |
20 A |
23 A |
Rated output frequency |
50 Hz / 60 Hz |
50 Hz / 60 Hz |
50 Hz / 60 Hz |
Output frequency range |
47-53 Hz / 57-63 Hz |
47-53 Hz / 57-63 Hz |
47-53 Hz / 57-63 Hz |
Total current harmonic distortion |
< 3% |
< 3% |
< 3% |
Max AC cable |
16 mm² copper |
16 mm² copper |
16 mm² copper |
AC connection type |
AC quick fit connector |
AC quick fit connector |
AC quick fit connector |
Output protection |
Anti-islanding protection, max external AC overcurrent protection, output overvoltage protection |
|
|
Operating Performance |
|
|
|
Maximum efficiency |
98.4% |
98.5% |
98.5% |
Weighted efficiency (EURO) |
98.1% |
98.2% |
98.2% |
Communication |
|
|
|
Embedded interfaces |
Double Ethernet port, WLAN, RS485 port |
|
|
Communication protocol |
Modbus TCP Sunspec, Modbus RTU Sunspec |
|
|
User interface |
LEDs, Web UI, Installer APP, optional display |
|
|
Cloud services |
Aurora Vision® Plant Management Platform, Rest API |
|
|
Advanced features |
Export limitation control, 24h self-consumption monitoring |
|
|
Environmental |
|
|
|
Ambient temperature range |
-25...+60°C |
-25...+60°C |
-25...+60°C |
Relative humidity |
4%-100% with condensation |
4%-100% with condensation |
4%-100% with condensation |
Max operating altitude |
4000 m with derating above 2000 m |
4000 m with derating above 2000 m |
4000 m with derating above 2000 m |
Physical |
|
|
|
Inverter type |
Grid connected, double stage, transformerless |
|
|
Environmental protection rating |
IP65 |
IP65 |
IP65 |
Environmental classification |
4K26 (IEC 60721-3-4) |
4K26 (IEC 60721-3-4) |
4K26 (IEC 60721-3-4) |
Cooling |
Natural cooling |
Natural cooling |
Natural cooling |
Dimension (H x W x D) |
568.2 x 473.6 x 207 mm |
568.2 x 473.6 x 207 mm |
568.2 x 473.6 x 207 mm |
Weight |
29.6 kg |
29.6 kg |
29.6 kg |
Mounting system |
Mounting bracket |
Mounting bracket |
Mounting bracket |
Safety |
|
|
|
Marking |
CE, RCM |
CE, RCM |
CE, RCM |
Safety and EMC standards |
IEC/EN 62109-1, IEC/EN 62109-2, EN 61000-6-1, EN 61000-6-2, EN 61000-3-11, EN 61000-3-12, EN 62311, EN 301 489-1, EN 301 489-17, EN 300 328 |
|
|