Overview

The INGECON® SUN 110TL M9 is a three-phase PV inverter designed for industrial self-consumption systems. It features nine independent Maximum Power Point Trackers (MPPT) and a DC/AC power conversion stage to optimize energy from the PV modules, even in challenging conditions such as scattered clouds and partial shading.

Key Features

  • Maximum Efficiency: 98.2% with nine independent MPPT inputs.
  • Plug & Play Technology: Fast and easy installation with country-specific configuration via App or PC.
  • Rugged Design: Designed for indoor and outdoor applications (IP66).
  • Ease of Maintenance: Internal datalogger, remote and on-site control, and LED status indicators.
  • Software Included: INGECON® SUN Monitor and iSun Monitor for monitoring and recording inverter data over the internet.
  • Communications: Ethernet and Wi-Fi as standard.
  • Warranty: Standard 5-year warranty, extendable up to 25 years.

Main Features

  • EMS inside.
  • Multi-MPPT system.
  • 98.2% maximum efficiency.
  • Digital inputs.
  • Ethernet and Wi-Fi communications supplied as standard.
  • Remote configuration and upgrade.
  • Software INGECON® SUN Monitor for PV plant monitoring.
  • LED Status.
  • Easy maintenance.
  • Plug & Play technology.
  • Suitable for indoor and outdoor installations (IP66).
  • High temperature performance.
  • Compact design.
  • Configurable language, rated voltage, and country code via App.
  • Compatible with high power modules (500W-600W+).

Protections

  • Reverse polarity protection.
  • Short circuits and overloads at the output.
  • Anti-islanding with automatic disconnection.
  • Insulation faults.
  • Input and output overvoltages with type II surge arresters.

Optional Accessories

  • Self-consumption kit.

Benefits

  • Greater performance thanks to the multi MPPT system.
  • Easy maintenance.
  • Higher inverter life expectancy.
  • Waterproof and dustproof (IP66).
  • Anti-corrosion with C4 protection class.

All models feature DC and AC surge arresters type II and an integrated DC switch.

Technical Specifications

Specification 110TL M9
Input (DC)
Recommended PV array power range 113.3 - 165 kWp
Voltage range MPPT 200 - 1,000 V
Maximum voltage 1,100 V
Rated input voltage 600 V
Start input voltage / Min. operating voltage 250 V / 200 V
Max. Short circuit current 3x50A + 6x45A
Maximum current 3x40A + 6x32A
Inputs with PV connectors 18 (9x2)
Number of MPPTs 9
Output (AC)
Rated power 110 kW
Max. apparent power (1) 123 kVA
Max. active power (PF = 1) (1) 121 kW
Max. output current 187 A
Rated voltage 400 V
Voltage range (2) 322 V - 520 V (Adjustable)
Frequency 50 / 60 Hz
Type of grid TT / TN / IT
Power Factor adjustable Yes, 0 - 1 (leading / lagging)
Efficiency
Maximum efficiency 98.2%
Euroefficiency 97.8%
General Information
Refrigeration system Forced ventilation
Consumption at night < 10 W
Ambient temperature -25°C to 60°C
Relative humidity (non-condensing) 0 - 100%
Protection class IP66
Marking CE
Acoustic emissions < 65 dB
Max. Operating altitude 4,000 m
EMC and security standards EN 61000-6-2, EN 61000-6-4, EN 62109-1, EN 62109-2
Grid connection standards IEC 61727:2004, IEC 62116:2014, EN 50549-1:2019, EN 50549-2:2019, UNE 217002:2020, UNE 217001:2020, NTS SEPE 2.1 type B, CEI 0-21 v1 November 2022 (including Allegato B), CEI 0-16 v1 November 2022 (including Allegato N), VDE-AR-N 4105:2018, DIN VDE V 0124-100/06.20
Integrated Elements
DC switch Yes
Anti-islanding protection Yes
AC overcurrent protection Yes
AC short-circuit protection Yes
DC reverse connection Yes
DC & AC surge arresters, type II Yes
Insulation detection Yes
Leakage current protection Yes
PV String monitoring Yes
Night load consumption monitoring Yes

Dimensions and Weight

  • 110TL M9:
    • Dimensions: 936 x 678 x 365 mm
    • Weight: 92 kg

Notes

  • In Spain, the maximum active power will be the same as the rated power.
  • The range of output voltage and frequency may vary depending upon different grid codes.

For further information: