KACO Blueplanet 105 TL3 Inverter
Overview
The KACO Blueplanet 105 TL3 is a high-efficiency, transformerless three-phase string inverter designed for commercial and industrial PV systems. It is optimized for PV modules with 1000V and 1500V, providing cost-saving benefits due to its 400V line voltage and integrated section switches. The inverter employs silicon carbide technology for higher efficiency and overload capacity, making it suitable for decentralised designs or the 'Virtual Central' concept.
Key Features
-
Voltage Compatibility: Optimized for 1000V and 1500V PV modules.
-
Efficiency: Utilizes silicon carbide technology for maximum efficiency and overload capacity.
-
Remote Services: Lean commissioning and updates via remote services.
-
Design Flexibility: Suitable for decentralized design or 'Virtual Central' concept.
-
High Protection Class: IP66/NEMA 4X for robust outdoor use.
-
High Power Density: Easy handling and logistics due to compact design.
Technical Specifications
DC Input Data
Specification |
Value |
Max. recommended PV generator power |
157,500 W |
MPP range |
591 – 1,300 V |
Operating range |
563 – 1,450 V |
Rated DC voltage / start voltage |
620 V / 675 V |
Max. no-load voltage |
1,500 V |
Max. input current |
183 A |
Max. short circuit current Isc max |
300 A |
Number of MPP tracker |
1 |
Connection per tracker |
1 - 2 |
AC Output Data
Specification |
Value |
Rated output |
99,900 VA |
Max. power |
105,000 VA |
Line voltage |
380 V (3P+PE), 400 V (3P+PE), 415 V (3P+PE) |
Voltage range (Ph-Ph) |
300 – 478 V |
Rated frequency (range) |
50 Hz / 60 Hz (45 – 65 Hz) |
Rated current |
3 x 144.5 A |
Max. current |
3 x 152.0 A |
Reactive power / cos phi |
0 – 100% Snom / 0.30 ind. – 0.30 cap. |
Max. total harmonic distortion (THD) |
≤ 3% |
Number of grid phases |
3 |
General Data
Specification |
Value |
Max. efficiency |
98.9% |
European efficiency |
98.6% |
CEC efficiency |
98.5% |
Standby consumption |
< 10 W |
Circuitry topology |
Transformerless |
Mechanical Data
Specification |
Value |
Display |
LEDs |
Control units |
Webserver, supports mobile devices |
Interfaces |
Ethernet (Modbus TCP, Sunspec), RS485 (KACO-protocol), USB, optional: 4-DI |
Fault signalling relay |
Potential-free NOC max. 30 V / 1 A |
DC connection |
Cable lug, max. 240 mm² (0.372 in²) Cu or Al |
AC connection |
Cable lug, max. 240 mm² (0.372 in²) Cu or Al |
Ambient temperature |
-25 °C – +60 °C (Power derating at high ambient temperatures) |
Humidity |
0 – 100% |
Max. installation elevation |
3,000 m |
Min. distance from coast |
500 m |
Cooling |
Temperature controlled fan |
Protection class |
IP66 / NEMA 4X |
Noise emission |
59.2 dB (A) |
Dimensions (H x W x D) |
719 x 699 x 460 mm |
Weight |
78.2 kg |
Certifications
-
Safety: IEC 62109-1/-2, EN 61000-6-1/-2/4, EN 61000-3-11/-12, EN 55011 group 1, class A, EN 62920 Emission class A/Immunity class A
-
Grid Connection Rule Overview: Available on the homepage/download area
Versions
Feature |
S |
XL |
Number of DC inputs |
1 - 2 |
1 - 2 |
DC switch |
- |
✔ |
DC SPD |
Type 1 + 2 |
Type 1 + 2 |
AC SPD |
○ |
○ |
RS485 interface SPD |
○ |
○ |
Ethernet interface SPD |
○ |
○ |
PID Set |
○ |
○ |
- ✔ = Standard
- ○ = Upgradeable
Notes
- For detailed grid connection rules and additional information, refer to the manufacturer's homepage or download area.
- Technical data may be subject to changes; ensure to refer to the latest version available on the website.