Monitoring the Inverter - Fault Guide
Fault No. 10 - Overcurrent in Hardware
- Explanation: Hardware overcurrent detection.
- Cause: N/A
- Remedial Action: Please contact our Service department.
Fault No. 11 - Auxiliary Power Supply Operation
- Explanation: Power supply of control electronics has failed.
- Cause: N/A
- Remedial Action: Please contact our Service department.
Fault No. 16 - Overtemperature
- Explanation: The inverter is too hot.
- Cause: Poor dissipation of the heat generated by the inverter.
- Remedial Action: Check whether the flow of air around the heat sinks of the inverter is impeded/blocked.
Fault No. 24 - Internal, AFI Defective
- Explanation: The RCCBs built into the inverter.
- Cause: Hardware defect.
- Remedial Action: Please contact our Service department.
Fault No. 26, 35, 37 - Fault, Internal Grid Monitoring
- Explanation: Internal communication fault.
- Cause: Hardware defect.
- Remedial Action: Please contact our Service department.
Fault No. 27 - Auxiliary Power Supply Stdb
- Explanation: Too little insolation to enable the electronics to function.
- Cause: N/A
- Remedial Action: Wait until the level of insolation is high enough.
Fault No. 28 - Fault, ENS/MSD Data CP
- Explanation: Plausibility check on the measured values.
- Cause: N/A
- Remedial Action: Please contact our Service department.
Fault No. 32 - Fault, DC Symmetry
- Explanation: Symmetry error of the electrolytic capacitor of the intermediate DC link.
- Cause: Defective capacitor.
- Remedial Action: Please contact our Service department.
Fault No. 33, 34 - Offset Error in Standby/Operation
- Explanation: Offset current or voltage measurement in standby/during operation outside permissible range.
- Cause: N/A
- Remedial Action: Please contact our Service department.
Fault No. 38 - Fault, Relay Defective
- Explanation: Grid isolating relay defective.
- Cause: Hardware defect.
- Remedial Action: Please contact our Service department.
Fault No. 40 - Fault, RAM-Check NOK
- Explanation: RAM check on startup is not okay.
- Cause: N/A
- Remedial Action: Switch the inverter off and on again.
Fault No. 41 - Fault, MPP Controller
- Explanation: Too low an output at too high a DC voltage.
- Cause: Hardware defect.
- Remedial Action: Please contact our Service department.
Fault No. 42 - Fault, External
- Explanation: External fault.
- Cause: A fault from an external source has been reported via the inputs of the inverter.
- Remedial Action: Test the external source for faults.
Models: 25 25 50 55