(CTRL + F) hızlı arama için.

AEG AS-IC01-2 (12KW-30KW) Manual

AEG AS-IC01-2 Series Grid-Tied Three-Phase Inverter Overview


General Description

The AEG AS-IC01-2 series inverters are designed for residential and commercial PV systems, providing compact design and high efficiency for small and medium-size installations. These inverters offer easy operability and comprehensive monitoring options, making them a versatile choice for various solar installations.


Key Features

  • Compact Design: Ideal for medium-size installations with flexible planning.
  • Efficiency: High efficiency ratings, ensuring optimal energy conversion.
  • Monitoring and Management: Integrated global monitoring system compatible with portable devices.
  • Ease of Installation: Features like built-in DC switch for safe and easy installation.
  • Warranty: Standard 5-year product warranty, with optional extensions to 10, 15, or 20 years.

Technical Specifications

Input (DC)

Model AS-IC01-12000-2 AS-IC01-15000-2 AS-IC01-17000-2 AS-IC01-20000-2 AS-IC01-25000-2 AS-IC01-30000-2 AS-IC01-33000-2 AS-IC01-35000-2
Nominal DC Input Power (W) 12000 15000 17000 20000 25000 30000 33000 35000
Max. DC Input Power (W) 12500 15600 17500 20800 26000 31200 36000 38000
Max. DC Input Voltage (V) 1000 1000 1000 1000 1000 1000 1000 1000
Starting Voltage (V) 200 200 200 300 300 300 300 300
MPPT Operating Voltage Range (V) 180-800 180-800 180-800 280-800 280-800 280-800 280-800 280-800
Operation Voltage (V) 350-800 400-800 400-800 450-800 480-800 480-800 520-800 550-800
Number of MPPT / String per MPPT 2/3 2/3 2/3 2/3 2/3 2/3 2/4 2/4
Max. DC Current (A) per MPPT x Nr. of MPPT 19 x 2 21 x 2 23 x 2 25 x 2 30 x 2 33 x 2 33 x 2 33 x 2
Isc PV (A) 21 x 2 23.5 x 2 25.5 x 2 27 x 2 33 x 2 36 x 2 36 x 2 36 x 2
Maximum Backflow Current (A) 0 0 0 0 0 0 0 0
DC Switch Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated

Output (AC)

Model AS-IC01-12000-2 AS-IC01-15000-2 AS-IC01-17000-2 AS-IC01-20000-2 AS-IC01-25000-2 AS-IC01-30000-2 AS-IC01-33000-2 AS-IC01-35000-2
Rated Output Power (W) 12000 15000 17000 20000 25000 30000 33000 35000
Max. Apparent Power SEmax (VA) 12085 15350 17083 20023 25000 30010 33011 34994
Max. AC Output Current (A) 19.3 24.1 27.3 32.0 40.0 48.0 48.0 48.0
Maximum Output Overcurrent Protection (A) 38.2 47.7 54.0 63.3 79.1 95 95 95
Maximum Output Fault Current (A) 250A @ 41.6ms 250A @ 41.6ms 250A @ 41.6ms 472A @ 11.04ms 472A @ 11.04ms 472A @ 11.04ms 472A @ 11.04ms 472A @ 11.04ms
AC Inrush Current <10A <10A <10A <20A <20A <20A <20A <20A
Voltage (V) / Frequency (Hz) 230~400 Vac, 50/60 Hz 230~400 Vac, 50/60 Hz 230~400 Vac, 50/60 Hz 230~400 Vac, 50/60 Hz 230~400 Vac, 50/60 Hz 230~400 Vac, 50/60 Hz 230~400 Vac, 50/60 Hz 230~400 Vac, 50/60 Hz
Power Factor -0.8 ~ +0.8 (adjustable) -0.8 ~ +0.8 (adjustable) -0.8 ~ +0.8 (adjustable) -0.8 ~ +0.8 (adjustable) -0.8 ~ +0.8 (adjustable) -0.8 ~ +0.8 (adjustable) -0.8 ~ +0.8 (adjustable) -0.8 ~ +0.8 (adjustable)
THDi <3% (at rated power) <3% (at rated power) <3% (at rated power) <3% (at rated power) <3% (at rated power) <3% (at rated power) <3% (at rated power) <3% (at rated power)
AC Output Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE) Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE) Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE) Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE) Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE) Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE) Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE) Three-phase (L1, L2, L3, N, PE) / (L1, L2, L3, PE)

Mechanical Parameters

Model AS-IC01-12000-2 to AS-IC01-17000-2 AS-IC01-20000-2 to AS-IC01-35000-2
Dimensions (H x W x D, mm) 610 x 480 x 230 660 x 520 x 250
Weight (kg) 36 53
DC Terminal BC03A, BC03B BC03A, BC03B
Installation Wall-mounting Wall-mounting
Safety Certificates / EMC Category / Grid Standards IEC 62109-1 (ed.1), IEC 62109-2 (ed.1), EN 62109-1:2010, EN 62109-2:2011, EN 61000-6-3:2007+A1:2011, EN 61000-6-2:2005; (12-17 kW) VDE-AR-N 4105:2018, DIN VDE V 0124-100:20; (20-35 kW) EN 50549-1:2019 IEC 62109-1 (ed.1), IEC 62109-2 (ed.1), EN 62109-1:2010, EN 62109-2:2011, EN 61000-6-3:2007+A1:2011, EN 61000-6-2:2005; (12-17 kW) VDE-AR-N 4105:2018, DIN VDE V 0124-100:20; (20-35 kW) EN 50549-1:2019
Noise (dB) ≤55 ≤55

System

| Cooling | Air cooling | | Max. Efficiency (%) | 98.20 - 98.50 | | Euro-Efficiency (%) | 97.60 - 98.10 | | MPPT Efficiency (%) | 99.90 | | Protection Rating | IP65 | | Power Consumption at Night (W) | <1 | | Topology and Isolation Mode | Non-isolated, transformerless | | Operating Temperature | -25°C ~ +60°C (derate after 45°C) | | Relative Humidity | 4 ~100%, condensation | | Max. Altitude (m) | ≤2000 (derate if the altitude >2000) | | Overvoltage Protection Class and Safety Class | AC

, PV
; Safety Class I | | Protection | Input overvoltage protection, input overcurrent protection, DC isolation monitoring, DC monitoring, grounding fault current monitoring, grid monitoring, island protection, short circuit protection, overheating protection |

 

Display and Communication

| Display | LCD | | System Language | English, German, Dutch | | Communication | RS485 + WiFi (Standard), Ethernet (Optional) |

Bloga dön

İletişim formu