AEG AS-IC01 (40 kW-70 kW) Manual
Share
AEG AS-IC01 Series Grid-Tied Three-Phase Inverter Overview
General Description
The AEG AS-IC01 series inverters are designed for commercial PV systems, offering compact design and high efficiency for large-size installations. These inverters provide easy operability and comprehensive monitoring options, making them an ideal choice for various solar installations.
Key Features
- High Power Output: Ideal for large-size installations with flexible planning.
- Efficiency: High efficiency ratings, ensuring optimal energy conversion.
- Monitoring and Management: Integrated global monitoring system compatible with portable devices.
- Ease of Installation: Features like built-in DC switch for safe and easy installation.
- Warranty: Standard 5-year product warranty, with optional extensions to 10, 15, or 20 years.
Technical Specifications
Input (DC)
Model | AS-IC01-40000 | AS-IC01-50000 | AS-IC01-60000 | AS-IC01-70000 |
---|---|---|---|---|
Nominal DC Input Power (W) | 40000 | 50000 | 60000 | 70000 |
Max. DC Input Power (W) | 55000 | 66000 | 72000 | 77000 |
Max. DC Input Voltage (V) | 1100 | 1100 | 1100 | 1100 |
Starting Voltage (V) | 200 | 200 | 200 | 200 |
MPPT Operating Voltage Range (V) | 570-950 | 570-950 | 570-950 | 570-950 |
Operation Voltage (V) | 600-850 | 600-850 | 600-850 | 600-850 |
Number of MPPT / String per MPPT | 1 / 10 | 1 / 12 | 1 / 14 | 1 / 14 |
Max. DC Current (A) per MPPT x Nr. of MPPT | 74 x 1 | 90 x 1 | 120 x 1 | 132 x 1 |
Isc PV (A) | 81 | 99 | 132 | 132 |
Maximum Backflow Current (A) | 0 | 0 | 0 | 0 |
DC Switch | Integrated | Integrated | Integrated | Integrated |
Output (AC)
Model | AS-IC01-40000 | AS-IC01-50000 | AS-IC01-60000 | AS-IC01-70000 |
---|---|---|---|---|
Rated Output Power (W) | 40000 | 50000 | 60000 | 70000 |
Max. AC Output Current (A) | 63.5 | 72.5 | 96 | 96 |
Maximum Output Overcurrent Protection (A) | 125.7 | 143.5 | 190 | 190 |
Maximum Output Fault Current (A) | 1050A @ 4.75 ms | 1050A @ 4.75 ms | 1050A @ 4.75 ms | 1050A @ 4.75 ms |
AC Inrush Current | <200A | <200A | <200A | <200A |
Voltage (V) / Frequency (Hz) | 230 |
230 |
230 |
230 |
Power Factor | -0.8 ~ +0.8 (adjustable) | -0.8 ~ +0.8 (adjustable) | -0.8 ~ +0.8 (adjustable) | -0.8 ~ +0.8 (adjustable) |
THDi | <3% (at rated power) | <3% (at rated power) | <3% (at rated power) | <3% (at rated power) |
AC Output | Three-phase (L1, L2, L3, N, PE) | Three-phase (L1, L2, L3, N, PE) | Three-phase (L1, L2, L3, N, PE) | Three-phase (L1, L2, L3, N, PE) |
Mechanical Parameters
Model | AS-IC01-40000 to AS-IC01-70000 |
---|---|
Dimensions (H x W x D, mm) | 810 x 645 x 235 |
Weight (kg) | 52 |
DC Terminal | BC03A, BC03B |
Installation | Wall-mounting |
Safety Certificates / EMC Category / Grid Standards | EN 62109-1:2010, EN 62109-2:2011, EN 61000-6-3:2007+A1:2011, EN 61000-6-2:2005 |
Noise (dB) | ≤55 |
System
| Cooling | Air cooling | | Max. Efficiency (%) | 98.60 | | Euro-Efficiency (%) | 98.20 | | MPPT Efficiency (%) | 99.90 | | Protection Rating | IP65 | | Power Consumption at Night (W) | <1 | | Topology and Isolation Mode | Non-isolated | | Operating Temperature | -25°C ~ +60°C (derate after 45°C) | | Relative Humidity | 4 ~100%, condensation | | Max. Altitude (m) | ≤2000 (derate if the altitude >2000) | | Overvoltage Protection Class and Safety Class | AC
, PV ; Safety Class I | | Protection | Input overvoltage protection, input overcurrent protection, DC isolation monitoring, DC monitoring, grounding fault current monitoring, grid monitoring, island protection, short circuit protection, overheating protection |
Display and Communication
| Display | LCD | | System Language | English, German, Dutch | | Communication | RS485 + WiFi (Standard), Ethernet (Optional) |